Abstract:
In this paper, we do the seismic identification of nuclear emergency diesel generator by test method. Dynamic characteristics including orthogonal tri-axial fundamental frequencies and equivalent damping ratios were measured by using the white noise scanning method. Artificial seismic waves were generated according to the floor acceleration response spectrum provided by the owners. Furthermore, five OBE and one SSE shaking table tests for emergency diesel generator were done by using the artificial seismic waves as seismic inputs along the orthogonal tri-axial simultaneity. The results show that the emergency diesel generator satisfies the seismic requirements and there is no obvious change of its performances before and after the earthquake test.