制冷机房的隔振降噪设计
Design on Vibration and Noise Control for the Refrigerator Room
摘要:
根据某大型写字楼制冷机房的噪声测试结果,为了降低振动影响,建立了具有中间质量块的双激励双输出二级隔振系统,通过调节隔振器中间质量块的重量调节二阶共振峰值的频率,达到增强隔振降噪效果的目的。经测试,制冷机房的噪声由92.3 dB (A)降低为68.7 dB (A),而且楼板振动明显减小,取到了良好的减振降噪效果。
Abstract:
According to the noise test results of a large office building’s refrigeration room, a double in- centive dual output vibration isolation system is established with intermediate masses in order to reduce vibration. Second-order resonance peak frequency can be changed by adjusting the inter- mediate mass weight of the isolator, and then improve the vibration isolation effect. By noise testing, the noise value in the refrigeration room is reduced from 92.3 dB (A) to 68.7 dB (A). Furthermore, the floor vibration is significantly reduced which indicates the effect of vibration and noise reduction is good.
参考文献
[1]
|
张雪梅, 宋文武. 中央空调系统消声与减振的研究[J]. 制冷与空调: 四川, 2012(3): 250-253.
|
[2]
|
巩云, 刘强, 卢军, 王亮. 成都东客站候车厅一体化空调射流机组噪声影响分析[J]. 暖通空调, 2010, 40(9): 29-33.
|
[3]
|
乐有奋, 潘茜, 傅建勋, 叶鸣. 某厂房暖通空调节能设计及室内噪声和空气污染控制[J]. 暖通空调, 2010, 40(9): 1-5.
|
[4]
|
周勃, 陈长征, 王长龙, 等. 冷却塔的噪声控制研究. 暖通空调, 2007, 37(3): 75-78.
|
[5]
|
杜力, 赵鹏云. 中央空调噪声分析及控制研究. 重庆工商大学学报, 2009, 26(3): 291-294.
|
[6]
|
计育根, 夏源龙, 胡仰耆. 常用风冷式热泵机组和冷水机组的噪声测量和分析. 暖通空调, 1999, 29(3): 11-15.
|