3/2断路器接线方式下电流互感器接线计量误差分析
The Measurement Error Analysis of the Current Transformer Connection under Way in 3/2 Circuit Breaker Main Electrical Connection
DOI: 10.12677/SG.2017.71002, PDF, HTML, XML, 下载: 1,813  浏览: 4,187 
作者: 高利明*, 徐二强, 赵 岩, 史三省, 吴春红:国网河南省电力公司电力科学研究院,河南 郑州
关键词: 电流互感器和相接线误差分析Current Transformer And Phase Connection Error Analysis
摘要: 根据3/2断路器接线方式下电流互感器的“和相”接线特点,详细分析了并联运行电流互感器的“和电流”误差特性,以及提出了该接线方式下对电流互感器误差一致性和对电网运行方式的具体要求,以减小接线因素的影响。
Abstract: According to the “and phase” current connection characteristics of the transformer under way in 3/2 circuit breaker main electrical connection, the current transformer parallel operation “and current” error characteristics are analyzed in detail. In addition, the paper puts forward the error consistency of current transformer and the specific requirements for the operation mode of the grid in order to reduce the influence of the connection factors.
文章引用:高利明, 徐二强, 赵岩, 史三省, 吴春红. 3/2断路器接线方式下电流互感器接线计量误差分析[J]. 智能电网, 2017, 7(1): 9-15. https://doi.org/10.12677/SG.2017.71002

参考文献

[1] 常仕亮, 等. 3/2断路器接线计量方式的探讨[J]. 电工技术, 2011(5): 28-29.
[2] 国家电网公司营销部. 国家电网公司输变电工程通用设计电能计量装置分册学习读本[M]. 北京: 中国电力出版社, 2008.
[3] 宋继成. 220-500kV变电所接线设计[M]. 北京: 中国电力出版社, 2004.