International Conference on Measuring Technology & Mechatronics Automation

Fault line selection in non-solidly earthed network based on modulus maximum polar- ity

作者:
Y ZhangQ GongD Chen

关键词:
modulus maximum polarity fault line selection wavelet packet transform characteristic frequency band non-solidly earthed network

摘要:
Despite the big progress made in recent years in the research on transient fault line selection methods in non-solidly earthed network, these methods are still far from perfect. A new scheme for fault line selection in non-solidly earthed network based on the singularity detection and modulus maximum polarity theory is proposed. This scheme applies wavelet packet transform to fractionize the frequency bands of the zero sequence transient current and picks out the characteristic band according to energy maximum principle. Not affected by line parameters and the neutral grounding manner, the criterion also has the ability of enduring high transition resistance. Its validity has been verified by the EMTP/MATLAB simulation results.

在线下载

相关文章:
在线客服:
对外合作:
联系方式:400-6379-560
投诉建议:feedback@hanspub.org
客服号

人工客服,优惠资讯,稿件咨询
公众号

科技前沿与学术知识分享