文章引用说明 更多>> (返回到该文章)

计育根, 夏源龙, 胡仰耆. 常用风冷式热泵机组和冷水机组的噪声测量和分析. 暖通空调, 1999, 29(3): 11-15.

被以下文章引用:

  • 标题: 制冷机房的隔振降噪设计Design on Vibration and Noise Control for the Refrigerator Room

    作者: 董立国

    关键字: 制冷机房, 噪声治理, 振动, 功率流Refrigeration Room, Noise Control, Vibration, Power Flow

    期刊名称: 《Hans Journal of Civil Engineering》, Vol.5 No.5, 2016-09-28

    摘要: 根据某大型写字楼制冷机房的噪声测试结果,为了降低振动影响,建立了具有中间质量块的双激励双输出二级隔振系统,通过调节隔振器中间质量块的重量调节二阶共振峰值的频率,达到增强隔振降噪效果的目的。经测试,制冷机房的噪声由92.3 dB (A)降低为68.7 dB (A),而且楼板振动明显减小,取到了良好的减振降噪效果。 According to the noise test results of a large office building’s refrigeration room, a double in- centive dual output vibration isolation system is established with intermediate masses in order to reduce vibration. Second-order resonance peak frequency can be changed by adjusting the inter- mediate mass weight of the isolator, and then improve the vibration isolation effect. By noise testing, the noise value in the refrigeration room is reduced from 92.3 dB (A) to 68.7 dB (A). Furthermore, the floor vibration is significantly reduced which indicates the effect of vibration and noise reduction is good.