超高压GIS中快速暂态过电压的仿真分析
Simulation and Analysis of Very Fast Transient Overvoltage in Extra High Voltage GIS
DOI: 10.12677/TDET.2012.12007, PDF, HTML, XML, 下载: 3,096  浏览: 10,059 
作者: 何柏娜, 张新慧:山东理工大学电气与电子工程学院;赵云伟:山东工业职业学院电气工程系
关键词: 快速暂态过电压隔离开关残余电压仿真 Very Fast Transient Overvoltage; Disconnector; Residual Voltage; Simulation
摘要:

本文以南方某550 kV GIS电站为研究对象,GIS结构出发,建立相应的GIS内部结构模型,在单机单出线工况下,对GIS隔离开关操作引起的快速暂态过电压进行仿真。研究GIS的结构参数对快速暂态过电压的影响,并从GIS内部、外部等多角度来分析VFTO的影响因素。 Taking a 550kV Gas Insulation Switchger (GIS) substation in the South as the object of study, the corresponding GIS internal structure model was established according to the structure of GIS in the paper. In the single motor single line conditions, very fast transient overvoltage (VFTO) caused by disconnector in GIS are simulated. In the paper, the effect of structure parameters of GIS on VFTO was studied, and the influence factors of VFTO were analyzed from multiple perspectives, such as GIS internal and external factors, and so on.

 

文章引用:何柏娜, 赵云伟, 张新慧. 超高压GIS中快速暂态过电压的仿真分析[J]. 输配电工程与技术, 2012, 1(2): 41-45. http://dx.doi.org/10.12677/TDET.2012.12007

参考文献

[1] 衣立东, 吕世荣. 750 kV输变电示范工程施工关键技术的研究与应用[J]. 电网技术, 2006, 30(3): 51-56.
[2] 林莘, 李爽, 徐建源. 特高压GIS壳体过电压特性[J]. 沈阳工业大学学报, 2009, 31(6): 606-610.
[3] 刘青, 张玉峰, 施围. 800 kV GIS中变压器VFTO防护的研究[J]. 高压电器, 2007, 43(2): 122-124.
[4] V. V. Kumar, J. M. Thomas and M. S. Naidu. Influence of switching conditions on the VFTO magnitudes in a GIS. IEEE Transactions on Power Delivery, 2001, 16(4): 539-544.
[5] 尹晓芳, 于力, 刘广维. 封闭式组合电器隔离开关产生的过电压[J]. 中国电机工程学报, 2002, 22(7): 111-114.
[6] 林莘, 田驰. 超高压GIS隔离开关操作引起VFTO的研究[J]. 高压开关行业通讯, 2008, 1-2: 36-39.
[7] 曾昭华, 林集明, 班连庚等. 特快速暂态过电压及研究实例[J]. 电网技术, 1996, 20(3): 5-10.
[8] 谷定燮, 修木洪, 戴敏等. 1000 kV GIS变电所VFTO特性研究[J]. 高电压技术, 2007, 33(11): 27-32.
[9] 徐建源, 路璐, 林莘. 1100 kV GIS隔离开关的电场数值计算与分析[J]. 高电压技术, 2008, 34(10): 2102-2106.
[10] 陈庆国, 张乔根, 邱毓昌等. GIS在快速暂态过电压下的放电特性[J]. 电网技术, 2000, 24(9): 1-4.