机房空调实验室风道结构模拟分析及实验验证
Simulation Analysis and Experimental Validation of Air Duct Structure in Air-Conditioned Laboratory of Machine Room
摘要: 机房空调实验室内流场的均匀性直接影响采集数据的精确度,而送风风道出风直接影响实验室内流场均匀性。针对机房空调实验室送风风道提出5种结构(分别是方形送风结构、10˚/12˚/14˚倾斜挡板送风结构以及等风量连续斜板送风结构),并建立几何模型进行数值模拟分析,选出对流场均匀性有较大改善的送风结构进行实验验证。结果表明:变截面积送风风道对流场的均匀性有一定的改善,尤其是对速度场的影响;14˚倾斜挡板送风结构的温度场和速度场的均匀性更好,在工程上易于实现,推荐使用该结构。
Abstract: The uniformity of the air flow field in the air-conditioning laboratory of the machine room directly affects the accuracy of the experiment data, and the air supply duct outlet directly affects the uni-formity of the air flow field in the laboratory. Five structures (the square air supply duct, the air duct supply 10˚, 12˚ and 14˚ inclined baffle respectively and the air supply duct with equal air volume continuous inclined plate) are proposed for the air supply ducts, the geometric models are established for numerical simulation analysis, and the air supply structure with greater im-provement on the uniformity of the flow field is selected for experimental verification. The results show that the variable cross-sectional area air duct can improve the uniformity of the air flow field, especially on the velocity field. The air supply duct with 14˚ inclined baffle is recommended because of the best uniformity of the temperature and velocity fields, which is realization in engineering application.
文章引用:闫龙超, 李征涛, 韩盼. 机房空调实验室风道结构模拟分析及实验验证[J]. 建模与仿真, 2021, 10(3): 693-704. https://doi.org/10.12677/MOS.2021.103070

参考文献

[1] 肖飚. 人工环境试验室空气流场与温度场的研究[D]: [硕士学位论文]. 南京: 南京工业大学, 2006.
[2] Sadrizadeh, S., Holmberg, S. and Tammelin, A. (2014) A Numerical Investigation of Vertical and Horizontal Laminar airflow Ventilation in an Operating Room. Building & Environment, 82, 517-525. [Google Scholar] [CrossRef
[3] Ye, W.B. (2017) Design Method and Modeling Verification for the Uniform Air Flow Distribution in the Duct Ventilation. Applied Thermal Engineering, 110, 573-583. [Google Scholar] [CrossRef
[4] Li, T.Y. (2017) On the Formulation of a 3-D Smooth Curved Pipe Finite Element with Arbitrary Variable Cross-Section. Thin-Walled Structures, 117, 314-331. [Google Scholar] [CrossRef
[5] Kefayati, G.H.R. and Huilgol, R.R. (2017) Lattice Boltzmann Meth-od for the Simulation of the Steady Flow of a Bingham Fluid in a Pipe of Square Cross-Section. European Journal of Mechanics B/Fluids, 65, 412-422. [Google Scholar] [CrossRef
[6] 杨志恒. 列车空调系统气候实验室气流组织研究[D]: [硕士学位论文]. 青岛: 青岛理工大学, 2015.
[7] 滕琴, 杨冬冬, 田奇勇, 等. 送风风道均匀送风的设计计算[J]. 流体机械, 2003, 31(1): 310-313.
[8] 肖婷, 李林, 梅硕俊, 等. 变截面风管均匀送风的气流组织CFD模拟[J]. 湖南工业大学学报, 2016, 30(2): 13-20.
[9] 戚新秋. 风道结构对人工环境试验室气流组织影响的研究[D]: [硕士学位论文]. 南京: 南京师范大学, 2018.
[10] 宋金蔚, 刘国丹, 李亮. 某列车送风系统及室内气流组织优化研究[J]. 青岛理工大学, 2015, 36(3): 72-78.
[11] 周晟杰. 人工环境试验室空气流场的研究[D]: [硕士学位论文]. 南京: 南京工业大学, 2008.
[12] Kim, D., Kwon, Y., Cho, Y., et al. (2009) Convective Heat Transfer Characteristics of Nanofluids under Laminar and Turbulent Flow Conditions. Current Applied Physics, 9, 119-123. [Google Scholar] [CrossRef
[13] 周凌九, 袁玲丽. 射流泵内部流动计算中不同湍流模拟方法的比较[J]. 排灌机械工程学报, 2013, 31(1): 25-30.
[14] Cortella, G., Manzan, M. and Comini, G. (2001) CFD Simu-lation of Refrigerated Display Cabinets. International Journal of Refrigeration, 24, 250-260. [Google Scholar] [CrossRef
[15] 全国冷冻空调设备标准化技术委员会. 计算机和数据处理机房用单元式空气调节机: GB/T 19413-2010 [S]. 北京: 中国标准出版社, 2011.
[16] 全国冷冻空调设备标准化技术委员会. 单元式空气调节机: GB/T 17758-2010 [S]. 北京: 中国标准化出版社, 2010.
[17] 全国人类工效学标准化技术委员会. 室内人体热舒适环境要求与评价方法: GB/T33658-2017 [S]. 北京: 中国标准出版社, 2017.