麓谷机房热管节能改造分析
Analysis of Heat Pipe Energy Saving Transformation in Lu-Valley Machine Room
DOI: 10.12677/MOS.2022.116143, PDF,   
作者: 肖 旭*:广东申菱热储科技有限公司,广东 佛山;肖伟雄#:衡阳市环境卫生事务中心,湖南 衡阳;陈飞虎:湖南大学土木工程学院,湖南 长沙
关键词: IDC (Information Data Center)机房热管有限时间热力学能效分析IDC (Information Data Center) Machine Room Heat Pipe Finite Time Thermodynamics Efficiency Analysis
摘要: 在2030“碳达峰”及2060年的“碳中和”背景下,各行业纷纷出台各项标准与应用低碳技术以响应国家政策。而IDC (Information Data Center)机房其能耗呈井喷式增长,节能降耗迫在眉睫。针对该形式,日前省发改委出台了“数据中心及5G基站”低碳行动方案。热管自然冷却是降低这一能耗的有效方法之一,目前单元式水冷多联热管系统被广泛应用于数据中心。本文针对长沙地区麓谷电信机房热管空调改造项目进行建模分析,并以实测值验证。结果表明,系统的年节电约为190万度。是值得在全国范围推广的技术。
Abstract: Under the background of “carbon peak” in 2030 and “carbon neutrality” in 2060, various industries have issued various standards and applied low-carbon technologies in response to national policies. However, the energy consumption of IDC (Information Data Center) machine rooms is increasing in a blowout way, and energy conservation and consumption reduction are imminent. In view of this form, the Provincial Development and Reform Commission recently issued a low-carbon action plan of “data center and 5G base station”. The natural cooling of heat pipe is one of the effective methods to reduce this energy consumption. At present, the unitary water-cooled multiple heat pipe system is widely used in the data center. In this paper, the modeling and analysis of the Lu-Valley telecommute-room heat pipe air conditioning reconstruction project in Changsha area are carried out, and verified by the measured values. The results show that the annual power saving of the system is about 1.9 million kilowatt hours. It is a technology worth popularizing nationwide.
文章引用:肖旭, 肖伟雄, 陈飞虎. 麓谷机房热管节能改造分析[J]. 建模与仿真, 2022, 11(6): 1524-1531. https://doi.org/10.12677/MOS.2022.116143

参考文献

[1] 齐蓉, 陈飞虎, 杨志新, 邢利, 廖曙光. 长沙地区某联通机房热管空调改造的节能分析[J]. 电力与能源进展, 2022, 10(4): 91-97.
[2] 陈飞虎, 廖曙光. 单元式水冷多联热管系统参数的MATLAB求解算法[J]. 洁净与空调技术, 2022(4): 1-3.
[3] 隆先进, 陈飞虎, 廖曙光. 热力学仿真软件CYCLEPAD在实际热力系统中的应用现状及展望[J]. 暖通空调, 2022, 2(增刊1): 286-288.
[4] 陈飞虎, 周新力, 廖曙光. 重力热管型双循环空调在夏热冷地区应用探讨[J]. 洁净与空调技术, 2022(1): 44-49.
[5] Chen, F.H., Liao, S.G. and Gong, G.C. (2022) Finite Time Thermodynamic Analysis and Optimization of Water Cooled Multi-Spilit Heat Pipe System (MSHPS). Energy and Built Environment, 3, 373-383. [Google Scholar] [CrossRef
[6] 陈飞虎, 廖曙光. 数据中心热管空调系统仿真研究——基于热力学模拟软件CYCLPAD [J]. 制冷与能源, 2016(2): 31-35.
[7] 王文华, 陈林根, 戈延林. 燃气轮机循环有限时间热力学研究新进展[J]. 海军工程大学学报, 2012, 41(3): 171-178.
[8] Wang, H.D. and Zhai, Z.Q. (2016) Advances in Building Simulation and Computational Techniques: A Review between 1987 and 2014. Energy and Buildings, 128, 319-335. [Google Scholar] [CrossRef
[9] Ling, L., Zhang, Q. and Yu, Y.B. (2017) Simulation of a Micro Channel Separate Heat Pipe (MCSHP) under Low Heat Flux and Low Mass Flux. Applied Thermal Engineering, 119, 25-33. [Google Scholar] [CrossRef
[10] Zhang, H.N. and Shao, S.Q. (2015) Integrated System of Mechanical Refrigeration and Thermosyphon for Free Cooling of Data Centers. Applied Thermal Engineering, 75, 185-192. [Google Scholar] [CrossRef
[11] 吕冬彦. 空气源热泵结霜工况性能分析与实验研究[D]: [硕士学位论文]. 长沙: 湖南大学, 2008.
[12] Li, G.Q., et al. (2016) Performance Analysis on a Solar Concentrating Thermoelectric Generator Using the Micro- Channel Heat Pipe Array. Energy Conversion and Management, 112, 191-198. [Google Scholar] [CrossRef