Digital fault location for parallel double-circuit multi-terminal trans-mission lines

作者:
T FunabashiH OtoguroY MizumaL Dube

关键词:
fault location power system analysis computing power transmission faults power transmission lines algorithms computer simulation current diversion ratio method digital fault location fault point location fault section currents

摘要:
Two new methods are proposed for fault point location in parallel double-circuit multi-terminal transmission lines by using voltages and currents information from CCVTs and CTs at all terminal. These algorithms take advantage of the fact that the sum of currents flowing into a fault section equals the sum of the currents at all terminals. Algorithm 1 employs an impedance calculation and algorithm 2 employs the current diversion ratio method. Computer simulations are carried out and applications of the proposed methods are discussed. Both algorithms can be applied to all types of fault such as phase-to-ground and phase-to-phase faults. As one equation can be used for all types of fault, classification of fault types and selection of faulted phase are not required. Phase components of the line impedance are used directly, so compensation of unbalanced line impedance is not required

在线下载

相关文章:
在线客服:
对外合作:
联系方式:400-6379-560
投诉建议:feedback@hanspub.org
客服号

人工客服,优惠资讯,稿件咨询
公众号

科技前沿与学术知识分享