《IEEE Transactions on Power Delivery》

Accurate Noniterative Fault Location Algorithm Utilizing Two-End Unsynchronized Measurements

作者:
J IzykowskiE RosolowskiP BalcerekM FulczykMM Saha

关键词:
electric current measurementfault locationphase measurementpower transmission faultspower transmission linessynchronisationvoltage measurementATP-EMTPaccurate noniterative fault location algorithmdistributed parameter line model

摘要:
This paper presents a new two-terminal impedance-based fault location algorithm, which takes into account the distributed parameter line model. The algorithm utilizes unsynchronized measurements of voltages and currents from two ends of a line and is formulated in terms of the fundamental frequency phasors of symmetrical components of the measured signals. First, an analytical synchronization of the unsynchronized measurements is performed with use of the determined synchronization operator. Then, the distance to fault is calculated as for the synchronized measurements. Simultaneous usage of two kinds of symmetrical components for determining the synchronization operator makes that the calculations are simple, noniterative and at the same time highly accurate. The developed fault location algorithm has been thoroughly tested using signals of ATP-EMTP versatile simulations of faults on a transmission line. The presented evaluation shows the validity of the developed fault location algorithm and its high accuracy.

在线下载

相关文章:
在线客服:
对外合作:
联系方式:400-6379-560
投诉建议:feedback@hanspub.org
客服号

人工客服,优惠资讯,稿件咨询
公众号

科技前沿与学术知识分享